Case: T09FR01128

Parcel: 131092340


Addresses:

1829 S CRAYCROFT RD

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/02/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Chapter 906, Portable Fire Extinguishers
TFC 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Professional maintenance yearly, manual inspection monthly, affix a tag to the extinguisher with records of these activities.)

_____ Have all extinguishers professionally maintained and manually inspected every 30 days thereafter with records of these activities indicated on an affixed tag.

TFC 906.3 - Size and distribution.
...Fire extinguishers for occupancies involving flammable or combustible liquids with depths of less than or equal to 0.25-inch shall be selected and placed in accordance with Table 906.3(2)*. Fire extinguishers for occupancies involving flammable or combustible liquids with a depth of greater than 0.25-inch or involving combustible metals shall be selected and placed in accordance with NFPA 10**.
* Ordinary Hazard = 10B >30' (or 20B >50')
** Chapter 6.3.2.3 - For flammable liquids hazards of appreciable depth, a Class B fire extinguisher shall be provided on the basis of at least 2 numerical units of Class B extinguishing potential per ft2 of flammable liquid surface of the largest hazard area.
6.3.2.7 - Travel distances for portable fire extinguishers shall not exceed 50 ft.
6.3.2.7.1 - Scattered or widely separated hazards shall be individually protected.

TFC 906.5 - Conspicuous location.
Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.

TFC 906.6 - Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.

TFC 906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
TFC 906.9 - Height above floor.
Portable fire extinguishers having a gross weight not exceeding 40 shall be installed so that its top is not more than 5 feet above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds shall be installed so that its top is not more than 3.5 feet above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches.

_____ Provide and mount extinguishers in an approved manner