Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/23/2009

Applicant:

MVL INVESTMENTS LLC

Description:

Full Inspection conducted 3/19/09 Business Representative: Mike Manore I have received a copy of this report and understand the corrections needed: ________________ Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Re-inspection: __/__/__ (or after). Approved ____________

Outstanding Inspections

Case Number: T09FR01040
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
03/19/2009 VIOL - PRECAUTION AGAINST FIRE DGREENLE Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained ... a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ Provide 18" clearance for sprinkler heads in freezer.
03/19/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.3 - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
03/19/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.3.1 - Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. _____ Provide signage for electrical room.
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation TFC 901.6.2 - Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. _____ Provide a copy of your most recent sprinkler report. (system tagged Sept. '09 by Metro)
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation TFC 904.11.6.3 - Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ Clean hood system in deli and keep records of periodical cleanings.
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation TFC 904.11.6.4 - Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____ Provide a copy of your most recent hood system report. (system tagged _____ by Wildcat)
03/25/2009 VIOL - ADMINISTRATION DGREENLE Violation TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. _____ Exit Sign Illumination _____ Repair Emergency Light
04/13/2009 INSP - REINSPECTION DGREENLE Partial Approval Waiting for fax confirming completion of work on _____ alarm system test deficiencies _____ E-light repair

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01040
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/19/2009 INSP - FULL DGREENLE Approved Initial Inspection 3/19/09 generated by Complaint T09FR00973 NO EXITING VIOLATIONS NOTED