Case: T09FR01040

Parcel: 13110034A


Addresses:

5500 E 22ND ST

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
03/19/2009 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3 - Working space and clearance.
A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear area around electrical panels and transformer.
03/19/2009 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3.1 - Labeling.
Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording.

_____ Provide signage for electrical room.