Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR01040

Parcel: 13110034A


Addresses:

5500 E 22ND ST


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01040

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 - Inspection, testing and maintenance.
Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11.6.3 - Cleaning.
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.

_____ Clean hood system in deli and keep records of periodical cleanings.
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6.2 - Records.
Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.

_____ Provide a copy of your most recent sprinkler report.
(system tagged Sept. '09 by Metro)
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11.6.4 - Extinguishing system service.
Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

_____ Provide a copy of your most recent hood system report.
(system tagged _____ by Wildcat)