Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/12/2009

Applicant:

TRU 2005 RE I LLC

Description:

Full Fire Prevention Inspection. Tori Koenneker 293-8960

Outstanding Inspections

Case Number: T09FR00595
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
02/12/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. _____1. The address numbers located on the southeast corner of the building shall be painted black to contrast with the building color.
02/12/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____1. Remove all brush from obstructing the (FDC) ,fire department connection, located on the south side of the building. _____2. Remove the storage from obstructing the sprinkler system inspector's test valve and drain valve located in the computer room.
02/12/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____1. Post a permanent, durable sign on the sprinkler system riser room door stating, "RISER ROOM".
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. _____1. Post a permanent, durable sign on the outside of the electrical equipment room door stating," ELECTRICAL ROOM".
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 604.4 Operational inspection and testing. Emergency power systems, including all appurtenant components shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111. _____1. Provide documentation of the current emergency generator test and inspection.
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove the storage from obstructing the electrical service equipment working space located in the computer room.
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. The exposed electrical wiring located in the tower area on the east wall shall have an approved cover. _____2. The trash compactor electrical connection shall have an approved cover.
02/12/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Provide a copy of the current sprinkler system inspection report. _____2. Provide a copy of the current fire alarm system inspection report. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
02/12/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double-keyed lock from the "customer pick up" door. NOTE: Replace it with a thumb-turn deadbolt.
02/12/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. Replace the burned out EXIT sign bulb located above the south EXIT door in the "Action" area.
02/12/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1. Replace the broken panic hardware handle located on the north EXIT door by the break room.
02/12/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. The north exit sign located outside shall be turned to face the correct direction.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00595
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/02/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code vioations have been corrected.