Case: T09FR00595

Parcel: 10408053K


Addresses:

4525 N ORACLE RD

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.

_____1. The exposed electrical wiring located in the tower area on the east wall shall have an approved cover.

_____2. The trash compactor electrical connection shall have an approved cover.
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 604.4 Operational inspection and testing. Emergency power
systems, including all appurtenant components shall be
inspected and tested under load in accordance with NFPA 110
and NFPA 111.

_____1. Provide documentation of the current emergency generator test and inspection.
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

_____1. Post a permanent, durable sign on the outside of the electrical equipment room door stating," ELECTRICAL ROOM".
02/12/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.

_____1. Remove the storage from obstructing the electrical service equipment working space located in the computer room.