Inspection Status: Correction Required

Inspection History: VIOL - FIRE SERVICE FEATURES

Date Description Inspector Results Comments
02/12/2009 VIOL - FIRE SERVICE FEATURES Correction Required TFC 505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the
property. Address numbers shall be in accordance with Pima County address display requirements.

_____1. The address numbers located on the southeast corner of the building shall be painted black to contrast with the building color.
02/12/2009 VIOL - FIRE SERVICE FEATURES Correction Required TFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash,
storage and other materials or objects shall not be placed or
kept near fire hydrants, fire department inlet connections or
fire protection system control valves in a manner that would
prevent such equipment or fire hydrants from being immediately
discernible. The fire department shall not be deterred
or hindered from gaining immediate access to fire protection
equipment or fire hydrants.

_____1. Remove all brush from obstructing the (FDC) ,fire department connection, located on the south side of the building.

_____2. Remove the storage from obstructing the sprinkler system inspector's test valve and drain valve located in the computer room.
02/12/2009 VIOL - FIRE SERVICE FEATURES Correction Required TFC 510.1 Identification. Fire protection equipment shall be identified
in an approved manner. Rooms containing controls for
air-conditioning systems, sprinkler risers and valves, or other
fire detection, suppression or control elements shall be identified
for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently
installed and readily visible.

_____1. Post a permanent, durable sign on the sprinkler system riser room door stating, "RISER ROOM".