Outstanding Inspections

Case Number: T09FR00048
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
01/07/2009 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 313.1.1 Removal. The fire code official is authorized to require removal of fueled equipment from locations where the presence of such equipment is determined by the fire code official to be hazardous. _____1.Remove all the fuel from the fueld equipment located in the building. NOTE: Purchase a flammable liquids cabinet and store the fuel used to demonstrate the equipment use inside the cabinet.
01/07/2009 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.4 Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 1.75 inches (44.5 mm) in thickness. Storage shall not be placed on exposed joists. _____1. Remove all storage from under the stairways located on the north and south side of the building.
01/07/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1.Service and tag the fire extinguisher located upstairs and by the west exit door.
01/07/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.3.5 Security grilles. In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles. _____1.Remove the vertical sliding security grill from the west exit door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) _ _____________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
01/07/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1.Remove the double-keyed lock from the southwest security grill and replace it with a thumb-turn deadbolt.
01/07/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Repair or replace the broken emergency lighting unit located in the south storage room 1st floor.
01/07/2009 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be done by the following method: Secure containers, cylinders and tanks to a fixed object with one or more restraints. _____1.Secure the Helium cylinder located in the south storage room by the above stated method.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00048
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/20/2009 INSP - FULL JBURGE Approved EZ Cash Super Pawn was sited for non compliance on March 3, 2009 and was fined $500.00. All noted tucson Tucson Fire Code violations were abated on April 13, 2009.