Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2009 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | TFC 315.2.4 Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 1.75 inches (44.5 mm) in thickness. Storage shall not be placed on exposed joists. _____1. Remove all storage from under the stairways located on the north and south side of the building. |
|
| 01/07/2009 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | TFC 313.1.1 Removal. The fire code official is authorized to require removal of fueled equipment from locations where the presence of such equipment is determined by the fire code official to be hazardous. _____1.Remove all the fuel from the fueld equipment located in the building. NOTE: Purchase a flammable liquids cabinet and store the fuel used to demonstrate the equipment use inside the cabinet. |