Case: T09FR00048

Parcel: 10601004B


Addresses:

3939 N 1ST AV

Inspection Status: Correction Required

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
01/07/2009 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2.4 Attic, under-floor and concealed spaces. Attic,
under-floor and concealed spaces used for storage of combustible
materials shall be protected on the storage side as
required for 1-hour fire-resistance-rated construction.
Openings shall be protected by assemblies that are self-closing
and are of noncombustible construction or solid wood
core not less than 1.75 inches (44.5 mm) in thickness. Storage
shall not be placed on exposed joists.

_____1. Remove all storage from under the stairways located on the north and south side of the building.
01/07/2009 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 313.1.1 Removal. The fire code official is authorized to
require removal of fueled equipment from locations where
the presence of such equipment is determined by the fire
code official to be hazardous.

_____1.Remove all the fuel from the fueld equipment located in the building.
NOTE: Purchase a flammable liquids cabinet and store the fuel used to demonstrate the equipment use inside the cabinet.