Case: T09FR00048

Parcel: 10601004B


Addresses:

3939 N 1ST AV

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
01/07/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.

_____1.Repair or replace the broken emergency lighting unit located in the south storage room 1st floor.
01/07/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1.Remove the double-keyed lock from the southwest security grill and replace it with a thumb-turn deadbolt.
01/07/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.3.5 Security grilles. In Groups B, F, M and S,
horizontal sliding or vertical security grilles are permitted
at the main exit and shall be openable from the inside
without the use of a key or special knowledge or effort
during periods that the space is occupied. The grilles
shall remain secured in the full-open position during the
period of occupancy by the general public. Where two or
more means of egress are required, not more than
one-half of the exits or exit access doorways shall be
equipped with horizontal sliding or vertical security
grilles.

_____1.Remove the vertical sliding security grill from the west exit door.



________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


_


_____________________________
(Captain)

Full inspection done by Inspector John E. Bieg
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg