Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/06/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection. Fabiola Gonzalez 888-0138

Outstanding Inspections

Case Number: T09FR00037
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1.Remove all storage located within the working space of the electrical service equipment located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1.Remove the cube adapter located behind the register. NOTE: Plug the fused power strip directly into the electrical outlet.
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _____1.Remove the tape from the electrical panel breaker switches.
01/06/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1.Replace the missing ceiling tile located in the management area. _____2.Replace the missing ceiling tile located in the back room.
01/06/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1.The southwest exit sign shall be illuminated.
01/06/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.The southwest exit sign located by the exit door shall have emergency back-up power. _____1.Repair or replace the broken emergency lighting unit located in the back room on the north wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00037
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/19/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violation have been corrected.