Case: T09FR00037

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR00037

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated.

_____1.Remove the tape from the electrical panel breaker switches.
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube
adapters, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.

_____1.Remove the cube adapter located behind the register.
NOTE: Plug the fused power strip directly into the electrical outlet.
01/06/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.

_____1.Remove all storage located within the working space of the electrical service equipment located in the back room.




________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)

Full inspection done by Inspector John E. Bieg
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____