Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR00037
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2009 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1.The southwest exit sign shall be illuminated. |
|
01/06/2009 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.The southwest exit sign located by the exit door shall have emergency back-up power. _____1.Repair or replace the broken emergency lighting unit located in the back room on the north wall. |