Description:

SPRINKLER INSPECTION

Outstanding Inspections

Case Number: T08FR04187
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
11/05/2008 INSP - FULL EDESCHAI Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION, FEB.,5,2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE 1) SPRINKLERS THAT ARE 50 YEARS OLD SHALL HAVE A SAMPLE TESTED OR SHALL BE REPLACED AS PER NATIONAL FIRE PROTECTION STANDARDS. 2) THE ALARM CLAPPER VALVE IS NOT SEATING CORRECTLY AND THE ALARM BELL RINGS INTERMITTANTLY. IT SHALL BE REPAIRED OR REPLACED IF NECESSARY 3) MISSING CEILING TILES SHALL BE REPLACED