Case: T08FR04187
Case Details
Entered Date:
11/05/2008
Applicant:
VALLEY NATIONAL BANK OF PHOENIX
Description:
SPRINKLER INSPECTION
Outstanding Inspections
Case Number: T08FR04187
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/05/2008 | INSP - FULL | EDESCHAI | Correction Required | DURING THE ANNUAL FIRE SPRINKLER INSPECTION, FEB.,5,2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE 1) SPRINKLERS THAT ARE 50 YEARS OLD SHALL HAVE A SAMPLE TESTED OR SHALL BE REPLACED AS PER NATIONAL FIRE PROTECTION STANDARDS. 2) THE ALARM CLAPPER VALVE IS NOT SEATING CORRECTLY AND THE ALARM BELL RINGS INTERMITTANTLY. IT SHALL BE REPAIRED OR REPLACED IF NECESSARY 3) MISSING CEILING TILES SHALL BE REPLACED |