Description:

SPRINKLER INSPECTION

Outstanding Inspections

Case Number: T08FR04151
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
11/03/2008 INSP - FULL EDESCHAI Correction Required DURING THE AANUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE 1) IF THE MAIN CONTROL VALVE IS NOT IN A SECURE AREA IT SHALL BE SECURED WITH A LOCK AND CHAIN 2) THE FULL SPRINKLER SYSTEM SHALL BE MONITERED FOR WATER FLOW. A SECTION OF THE BUILDING IS SUPPLIED FROM A MECHANICAL T AT THE FIRE DEPT. CONNECTION. A WATER FLOW DEVICE FOR THIS AREA IS NOT CONNECTED 3) THE CEILING AT THE SECOND FLOOR SHALL HAVE BE REPLACED, TO FACILITATE HEAT COLLECTION IN THE EVENT OF A SITUATION 4) ALL CENTRAL, MODEL G. B. SPRINKLER HEADS ON THE 3RD. FLOOR, THAT ARE ON RECALL SHALL BE REPLACED