Case: T08FR02982
Case Details
Entered Date:
09/19/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection conducted 9/18/08
Outstanding Inspections
Case Number: T08FR02982
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2008 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Violation | SECTION 315 - MISCELLANEOUS COMBUSTIBLE MATERIALS STORAGE TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ remove boxes from top shelves (not against walls) in stock room |
09/19/2008 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Violation | TFC 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures. _____ Remove combustable storage from exit hallway |
09/19/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels and transformer. |
09/19/2008 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Violation | Opening protectives TFC 703.2 - Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Fire door assemblies shall not be modified. _____ Keep required fire doors closed |
09/19/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Replace ceiling tile in stockroom _____ All sprinkler heads shall be adjusted to meet the requirements of this code _____ Replace escutcheons in changing room _____ Replace escutcheons in "room 3" (x3) _____ Move speakers that are obstructing sprinkler heads to a distance (determined by the sprinkler contractor) that will not cause an imparement of the designed caverage pattern. |
09/19/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | Blocked exit: TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted... The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit hallway. |
09/19/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | Exit Signs TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
09/19/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | MEANS OF EGRESS ILLUMINATION 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Test and repair/replace emergency lighting as needed |
10/20/2008 | INSP - REINSPECTION | DGREENLE | Violation | delivered pre-citation - NEXT RI 11/3 |
10/20/2008 | INSP - REINSPECTION | DGREENLE | Violation | NO CORRECTIONS NOTED - PRE-CITATION SERVED |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02982
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: on file and posted Extinguishers: Tested, tagged and monthly inspection records are up to date |
11/04/2008 | COMPL - REINSPECTION | DGREENLE | Approved | speakers moved, all deficiencies corrected |