Case: T08FR02982

Parcel: 12801005H

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02982

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
09/19/2008 VIOL - MEANS OF EGRESS Violation Blocked exit:
TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted... The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_____ Clear exit hallway.
09/19/2008 VIOL - MEANS OF EGRESS Violation MEANS OF EGRESS ILLUMINATION
1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.

_____ Test and repair/replace emergency lighting as needed
09/19/2008 VIOL - MEANS OF EGRESS Violation Exit Signs
TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.

_____ Repair/replace exit signs