Case: T08FR02982

Parcel: 12801005H

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02982

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
09/19/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

_____ Replace ceiling tile in stockroom

_____ All sprinkler heads shall be adjusted to meet the requirements of this code

_____ Replace escutcheons in changing room

_____ Replace escutcheons in "room 3" (x3)

_____ Move speakers that are obstructing sprinkler heads to a distance (determined by the sprinkler contractor) that will not cause an imparement of the designed caverage pattern.