Case: T08FR02722
Case Details
Entered Date:
09/09/2008
Applicant:
TUCSON ST MARY'S PLAZA LLC
Description:
Full Fire Prevention Inspection Building Rep: Megan Mar Phone # 520-882-7100
Outstanding Inspections
Case Number: T08FR02722
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2008 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
| 09/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.4.1 Power tap design Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. _____ Remove the power tap adapter from the ceiling outlet in the main lobby. |
| 09/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective _____ Remove the sprinkler head near the hood system in the kitchen as it is completely covered in grease. |
| 09/09/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ The back south east egress door located in the kitchen has a secondary locking device that shall be disabled or removed. 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). 3. No additional locks or latches shall be added _____ Remove the turn knob with locking device from the north east door as no additonal locks shall be allowed to added to a door with panic hardware. |
| 09/09/2008 | VIOL - COMPRESSED GASES | JLONGO | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times (the one next to the ice machine) ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ____________________ Passed on: ________ (Joseph P. Longo) |