Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/02/2008

Applicant:

LDR-SILVERBELL LLC

Description:

Full Fire Prevention Inspection. David Rinker 624-7475

Outstanding Inspections

Case Number: T08FR02599
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1.Remove all storage from obstructing the electrical service equipment located in the kitchen.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Service and tag the automatic sprinkler system or provide documentation of such work being done within the last 12 months. _____2.Service and tag the Fire Alarm system or provide documentation of such work being done within the last 12 months. NOTE:The Fire Alarm system is in trouble status.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1.Clean and remove all accumulation from the hood systems and provide documentation of such work. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 905.9 Valve supervision. Valves controlling water supplies shall be supervised in the open position so that a change in the normal position of the valve will generate a supervisory signal at the supervising station required by Section 903.4. Where a fire alarm system is provided, a signal shall also be transmitted to the control unit. _____1.The automatic sprinkler system main control valve shall be locked in the open position with a chain and padlock.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. _____1.Properly mount the portable fire extinguisher located behind the counter by the soda machine.
09/02/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system... _____1.Repair or replace the emergency lighting unit located above the exit door in the kitchen.
09/02/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1.Remove all storage from obstructing the exit door located in the kitchen.
09/02/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1.Remove the thumb-turn lock from the Southwest exit door located by the game area.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02599
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/01/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.