Case: T08FR02599

Parcel: 115211520

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02599

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

_____1.Service and tag the automatic sprinkler system or provide documentation of such work being done within the last 12 months.

_____2.Service and tag the Fire Alarm system or provide documentation of such work being done within the last 12 months.
NOTE:The Fire Alarm system is in trouble status.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be
securely anchored to the mounting surface in accordance with
the manufacturer’s installation instructions.

_____1.Properly mount the portable fire extinguisher located behind the counter by the soda machine.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 905.9 Valve supervision. Valves controlling water supplies
shall be supervised in the open position so that a change in the
normal position of the valve will generate a supervisory signal
at the supervising station required by Section 903.4. Where a
fire alarm system is provided, a signal shall also be transmitted
to the control unit.

_____1.The automatic sprinkler system main control valve shall be locked in the open position with a chain and padlock.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

_____1.Clean and remove all accumulation from the hood systems and provide documentation of such work.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)




I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)

Full inspection done by Inspector John E. Bieg
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____