Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR02599

Parcel: 115211520

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02599

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/02/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

_____1.Remove the thumb-turn lock from the Southwest exit door located by the game area.
09/02/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency when the areas served by such exits are occupied.

_____1.Remove all storage from obstructing the exit door located in the kitchen.
09/02/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system...