Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/02/2008

Applicant:

PARK MALL LLC

Description:

Full Inspection 9/28/08

Outstanding Inspections

Case Number: T08FR02596
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
02/06/2009 VIOL - ADMINISTRATION DGREENLE Correction Required SECTION 107, MAINTENANCE TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device... or any other feature is required for compliance with the provisions of this code, or otherwise installed, (it) shall thereafter be continuously maintained. _____ Exit Sign Illumination
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear transformer and area in front of electrical panels.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove noncomplying devices.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove extension cord and/or replace with approved permanent electrical power source.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 609.1 - Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code. _____ Clean exhaust hood periodically to prevent the accumulation of dust.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation ELECTRICAL EQUIPMENT, WIRING AND HAZARDS TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated. _____ Exit sign in kitchen
09/02/2008 VIOL - MEANS OF EGRESS DGREENLE Violation Bolt locks TFC 1008.1.8.4 - Manually operated flush bolts or surface bolts are not permitted. _____ Remove non-compliant lock from kitchen door
09/02/2008 VIOL - COMPRESSED GASES DGREENLE Violation Compressed gas cylinders not secured: TFC 3003.3 - Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02596
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Approved TFC 906.6 - Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. _____ Provide signage indicating location of extiniguisher.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Approved Portable Fire Extinguishers TFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguisher shall be serviced annually, inspected monthly and tagged indicating the dates of those actions.
09/02/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy on file
03/09/2009 INSP - REINSPECTION DGREENLE Approved *** FINAL - APPROVED