Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02596

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
02/06/2009 VIOL - FIRE PROTECTION SYSTEMS Approved TFC 906.7 - Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

TFC 906.9 - Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

_____ Mount extinguishers in an approved manner.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS Violation Portable Fire Extinguishers
TFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.

_____ Extinguisher shall be serviced annually, inspected monthly and tagged indicating the dates of those actions.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 906.6 - Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.

_____ Provide signage indicating location of extiniguisher.