Case: T08FR02596

Parcel: 12801005H

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR02596

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS Violation ELECTRICAL EQUIPMENT, WIRING AND HAZARDS
TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____ Exit sign in kitchen
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear transformer and area in front of electrical panels.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove extension cord and/or replace with approved permanent electrical power source.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

_____ Remove noncomplying devices.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 609.1 - Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code.

_____ Clean exhaust hood periodically to prevent the accumulation of dust.