Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR02596
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | ELECTRICAL EQUIPMENT, WIRING AND HAZARDS TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated. _____ Exit sign in kitchen |
|
09/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear transformer and area in front of electrical panels. |
|
09/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove extension cord and/or replace with approved permanent electrical power source. |
|
09/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove noncomplying devices. |
|
09/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 609.1 - Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code. _____ Clean exhaust hood periodically to prevent the accumulation of dust. |