Case: T08FR02573
Case Details
Entered Date:
08/28/2008
Applicant:
RIO NUEVO MULTIPURPOSE FACILITIES DISTRICT
Description:
Full Fire Inspection. Doug Biggers 250-6423
Outstanding Inspections
Case Number: T08FR02573
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | 505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. _____1.Post the address numbers on the building in accordance with Pima County address display requirements. |
08/28/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1.The open wiring located on the bottom floor on the west wall shall have an approved cover. |
08/28/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the extension cord located in the auditorium concession area. NOTE:Replace it with a fused multi-plug adapter. _____2.Remove all extension cords located in the main office area. NOTE:Replace it with a fused multi-plug adapter. |
08/28/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1.Repair the holes in the walls located in the beer storage room. _____2.Repair the hole in the ceiling located above the west exit door by the stage. |
08/28/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1.Service and tag all portable fire extinguishers. _____2.Service and tag the automatic sprinkler system or provide documentation of the current sprinkler inspection report. |
08/28/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1.Remove the double-keyed lock from the egress door located in the office/restroom. NOTE:Replace it with a thumb-turn lock. _____2.Remove the double-keyed lock from the east side stage door NOTE:Replace it with a thumb-turn lock. _____3.Remove the double-keyed lock from the east under-stage basement door. NOTE:Replace it with a thumb-turn lock. _____4.Remove the double-keyed lock from the southwest side stage door NOTE:Replace it with a thumb-turn lock. |
08/28/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1025.11.3 Tread contrasting marking stripe. A contrasting marking stripe shall be provided on each tread at the nosing or leading edge such that the location of each tread is readily apparent when viewed in descent. Such stripe shall be a minimum of 1 inch (25 mm), and a maximum of 2 inches (51 mm), wide. TFC 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 foot-candle (11 lux) at the walking surface level. _____1.Provide photoluminescent egress products or floor lighting for all means of egress walking surfaces including the stair tread. |
08/28/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Repair or replace the non-functioning emergency lighting unit located in the green room. |
08/28/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1.Secure the compressed gas cylinder located behind the bar to a fixed object with one or more restraints. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02573
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |