Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR02573
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1.Remove the double-keyed lock from the egress door located in the office/restroom. NOTE:Replace it with a thumb-turn lock. _____2.Remove the double-keyed lock from the east side stage door NOTE:Replace it with a thumb-turn lock. _____3.Remove the double-keyed lock from the east under-stage basement door. NOTE:Replace it with a thumb-turn lock. _____4.Remove the double-keyed lock from the southwest side stage door NOTE:Replace it with a thumb-turn lock. |
|
08/28/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Repair or replace the non-functioning emergency lighting unit located in the green room. |
|
08/28/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1025.11.3 Tread contrasting marking stripe. A contrasting marking stripe shall be provided on each tread at the nosing or leading edge such that the location of each tread is readily apparent when viewed in descent. Such stripe shall be a minimum of 1 inch (25 mm), and a maximum of 2 inches (51 mm), wide. TFC 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 foot-candle (11 lux) at the walking surface level. _____1.Provide photoluminescent egress products or floor lighting for all means of egress walking surfaces including the stair tread. |