Case: T08FR02573

Parcel: 11706168C


Addresses:

318 E CONGRESS ST


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02573

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/28/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1.Remove the double-keyed lock from the egress door located in the office/restroom.
NOTE:Replace it with a thumb-turn lock.

_____2.Remove the double-keyed lock from the east side stage door
NOTE:Replace it with a thumb-turn lock.

_____3.Remove the double-keyed lock from the east under-stage basement door.
NOTE:Replace it with a thumb-turn lock.

_____4.Remove the double-keyed lock from the southwest side stage door
NOTE:Replace it with a thumb-turn lock.
08/28/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.

_____1.Repair or replace the non-functioning emergency lighting unit located in the green room.
08/28/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1025.11.3 Tread contrasting marking stripe. A contrasting
marking stripe shall be provided on each tread at the nosing
or leading edge such that the location of each tread is
readily apparent when viewed in descent. Such stripe shall
be a minimum of 1 inch (25 mm), and a maximum of 2
inches (51 mm), wide.

TFC 1006.2 Illumination level. The means of egress illumination
level shall not be less than 1 foot-candle (11 lux) at the walking
surface level.

_____1.Provide photoluminescent egress products or floor lighting for all means of egress walking surfaces including the stair tread.