Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR02573
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1.The open wiring located on the bottom floor on the west wall shall have an approved cover. |
|
08/28/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the extension cord located in the auditorium concession area. NOTE:Replace it with a fused multi-plug adapter. _____2.Remove all extension cords located in the main office area. NOTE:Replace it with a fused multi-plug adapter. |