Case: T08FR02489
Case Details
Entered Date:
08/21/2008
Applicant:
BRAKE MAX HOUGHTON AND VALENCIA LLC
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T08FR02489
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2008 | VIOL - ADMINISTRATION | NSPRENGE | Violation | IFC 105.6.16 An operational permit is required ... 2) To store, handle, or use Class I liquids in excess of 5 gallons in a building. You will apply for and acquire such permits. |
08/22/2008 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. |
08/22/2008 | VIOL - HAZARDOUS MATERIALS,GEN | NSPRENGE | Violation | IFC 2703.1.1 (1) Your maximum allowable quantity of a Class 1B Flammable Liquid inside a building is 120 gallons. You currently have 4 - 55 gallon drums of Brake Cleaner inside the building. Since you store/ use these from 55 gallon drums, you will only be able to have 2 drums inside the building. |
08/22/2008 | VIOL - COMPRESSED GASES | NSPRENGE | Violation | IFC 3003.5.3 Compressed gas cylinders, tanks, and containers, shall be secured to prevent falling cused by contact, vibration or seismic activity. Secure your freon tanks to a sturdy object to prevent falls. |
09/04/2008 | INSP - REINSPECTION | NSPRENGE | Correction Required | cylinders are not chained, emergency lighting is still not operating, there are now 4- 55 gal drums of Class 1B flammable liquidj; max quantity is 120 gals. Waiting for AST;s to be approved, needs to label waste drums with materials contained inside, Exit sign over the West shop door is removed as requested because not an acceptable exit, they have acquired metal can with self closing lid for dirty rags. Additionally, the closed dispensing system for the brake cleaner needs a automatic closing lever instead of a twist on/off. Very little has been done in two weeks. I gave one week for complliance before moving to pre-cite the business owner. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02489
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2008 | INSP - FULL | NSPRENGE | Approved | Permit for AST issued and all other violations have been ebated. |