Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR02489

Parcel: 14117007M


Addresses:

7525 S HOUGHTON RD


Inspection Status: Violation

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Case Number - T08FR02489

Inspection Description - VIOL - HAZARDOUS MATERIALS,GEN

Inspection Status - Violation

Date Description Inspector Results Comments
08/22/2008 VIOL - HAZARDOUS MATERIALS,GEN Violation IFC 2703.1.1 (1) Your maximum allowable quantity of a Class 1B Flammable Liquid inside a building is 120 gallons. You currently have 4 - 55 gallon drums of Brake Cleaner inside the building. Since you store/ use these from 55 gallon drums, you will only be able to have 2 drums inside the building.