Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR02489

Parcel: 14117007M


Addresses:

7525 S HOUGHTON RD


Inspection Status: Correction Required

Inspection History: INSP - REINSPECTION

Case Number - T08FR02489

Inspection Description - INSP - REINSPECTION

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/04/2008 INSP - REINSPECTION Correction Required cylinders are not chained, emergency lighting is still not operating, there are now 4- 55 gal drums of Class 1B flammable liquidj; max quantity is 120 gals. Waiting for AST;s to be approved, needs to label waste drums with materials contained inside, Exit sign over the West shop door is removed as requested because not an acceptable exit, they have acquired metal can with self closing lid for dirty rags. Additionally, the closed dispensing system for the brake cleaner needs a automatic closing lever instead of a twist on/off. Very little has been done in two weeks. I gave one week for complliance before moving to pre-cite the business owner.