Description:

Full Fire Inspection RAMON M WROUGHT IRON Building Rep: Ramon Martinez Jr. Phone # 623-5450 Cell Phone # 808-1328

Outstanding Inspections

Case Number: T08FR01643
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
06/18/2008 INSP - FULL JLONGO Correction Required Full Fire prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
06/18/2008 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.4 Multiplug adapters Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC electrical code shall be prohibited. _____ All multiplug adapters shall be removed and/or replace with approved fused power strips. 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. * All extension cords shall be used only for temporary use
06/18/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code
06/18/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation _____ One the main egress door: remove the pad lock, remove the slide bolt, and replace with a lock that meets the code requirments _____ One your secondary door: remove the slide bolt lock, and remove the double key lock
06/18/2008 VIOL - FLAMMABLE FINISHES JLONGO Correction Required 1503.2.6 Smoking prohibited. Smoking shall be prohibited in flammable vapor areas and hazardous materials storage rooms associated with flammable finish processes. "No Smoking" signs complying with Section 310 shall be conspicuously posted in such areas. 310.3 "No Smoking" signs. The fire code official is authorized to order the posting of "No Smoking" signs in a conspicuous location in each structure or location in which smoking is prohibited. The content, lettering, size, color and location of required "No Smoking" signs shall be approved. _____ Approved "NO SMOKING" signs shall be placed in the main building and in the spray booth area. 1504.4 Fire protection. Spray booths and spray rooms shall be protected by an approved automatic fire extinguishing system complying with Chapter 9. Protection shall also extend to exhaust plenums, exhaust ducts and both sides of dry filters when such filters are used. 1504.4.1 Fire extinguishers. Portable fire extinguishers complying with Section 906 shall be provided for spraying areas in accordance with the requirements for an extra (high) hazard occupancy. _____ A fire sprinkler system will need to be installed into your spray booth as long as you continune to use flammable oil based paint _____ A portable fire exstingusher shall be placed into the spray booth area
06/18/2008 VIOL - FLAMMABLE LIQUIDS JLONGO Correction Required 3404.4.2.4 Storage adjacent to buildings. A maximum of 1,100 gallons (4163 L) of liquids stored in closed containers and portable tanks is allowed adjacent to a building located on the same premises and under the same management, provided that: 1. The building does not exceed one story in height. Such building shall be of fire-resistance-rated construction with noncombustible exterior surfaces or noncombustible construction and shall be used principally for the storage of liquids; or 2. The exterior building wall adjacent to the storage area shall have a fire-resistance rating of not less than 2 hours, having no openings to above-grade areas within 10 feet (3048 mm) horizontally of such storage and no openings to below-grade areas within 50 feet (15 240 mm) horizontally of such storage. 3404.4.4 Security. Storage areas shall be protected against tampering or trespassers by fencing or other approved control measures. 3404.4.6 Clearance from combustibles. The storage area shall be kept free from weeds, debris and combustible materials not necessary to the storage. The area surrounding an exterior storage area shall be kept clear of such materials for a minimum distance of 15 feet (4572 mm). _____ You are over the maximum allowed 30 gallons permitted for your oil based paint. You must remove, dipose, and/or place your excess piant in seperate room according to the codes stated above. *** There is no limitation on storage for water-based paint *** If a storage room is choosen, then proper security and clearance from combustibles shall be followed. I.E A lock shall be placed on the storage room and the yard shall be maintained. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo