Case: T08FR01643

Parcel: 107143400


Addresses:

307 E GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR01643

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/18/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation

_____ One the main egress door: remove the pad lock, remove the slide bolt, and replace with a lock that meets the code requirments

_____ One your secondary door: remove the slide bolt lock, and remove the double key lock