Case: T08FR00567
Case Details
Entered Date:
02/27/2008
Applicant:
K&E BUILDINGS FAMILY LLLP
Description:
FULL FIRE INSPECTION.
Outstanding Inspections
Case Number: T08FR00567
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | VIOL - PRECAUTION AGAINST FIRE | JVINCENT | Violation | 304.1.1 Waste material. Accumulations of wastepaper, wood, hay, straw, weeds, litter or combustible or flammable waste or rubbish of any type shall not be permitted to remain on a roof or in any court, yard, vacant lot, alley, parking lot, open space, or beneath a grandstand, bleacher, pier, wharf, manufactured home, recreational vehicle or other similar structure. ____ Remove waste material from rear of property. |
| 02/27/2008 | VIOL - PRECAUTION AGAINST FIRE | JVINCENT | Violation | 304.1.2 Vegetation. Weeds, grass, vines or other growth that is capable of being ignited and endangering property, shall be cut down and removed by the owner or occupant of the premises. Vegetation clearance requirements in urban-wildland interface areas shall be in accordance with the International Wildland-Urban Interface Code. ____ Remove dry vegetation around electrical panels located in rear. |
| 02/27/2008 | VIOL - PRECAUTION AGAINST FIRE | JVINCENT | Violation | 311.3 Removal of combustibles. Persons owning, or in charge or control of, a vacant building or portion thereof, shall remove therefrom all accumulations of combustible materials, flammable or combustible waste or rubbish and shall securely lock or otherwise secure doors, windows and other openings to prevent entry by unauthorized persons. The premises shall be maintained clear of waste or hazardous materials. ____ Remove all waste material from shed. |
| 02/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Violation | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ____ Open wires, front sign. ____ Open wires, main room hanging from ceiling. ____ Open wires, south shop. On floor, west wall and south wall. ____ Cover plate for outlets needed x 3 in center office room. ____ Cover plate needed for exterior/rear electrical box. |
| 02/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. ____ Provide an appropriate working space in front of electrical equipment. |
| 02/27/2008 | VIOL - FIRE RESIST.RATED CONST | JVINCENT | Violation | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. ____ Repair all holes in ceiling and walls. |
| 02/27/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____ Service and tag extinguishers. |
| 02/27/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____ Only one key lock allowed on main exit door. ____ Remove double keyed deadbolts from all other exit doors. Replace with thumbturn locks. Only one per door allowed. |
| 02/27/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, ____ Provide a sign above front exit doors. |
| 02/27/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ____ Remove slide bolts from shop doors. |
| 02/27/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | 1027.4 Power source. Where emergency illumination is required in Section 1027.5, exit signs shall be visible under emergency illumination conditions. ____ Repair both exit signs. Back up battery power did not work. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00567
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2009 | INSP - FULL | JVINCENT | Approved | BUILDING SOLD. COMPLETE REMODEL IN THE WORKS. |