Case: T08FR00567

Parcel: 12605024B


Addresses:

4020 E SPEEDWAY BL

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
02/27/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:
2. In buildings in occupancy Group A having an
occupant load of 300 or less, Groups B, F,Mand S,
and in places of religious worship, the main exterior
door or doors are permitted to be equipped
with key-operated locking devices from the egress
side provided:
2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background,

____ Provide a sign above front exit doors.
02/27/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

____ Only one key lock allowed on main exit door.
____ Remove double keyed deadbolts from all other exit doors. Replace with thumbturn locks. Only one per door allowed.
02/27/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or
surface bolts are not permitted.

____ Remove slide bolts from shop doors.
02/27/2008 VIOL - MEANS OF EGRESS Violation 1027.4 Power source. Where emergency illumination is
required in Section 1027.5, exit signs shall be visible under
emergency illumination conditions.

____ Repair both exit signs. Back up battery power did not work.