Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ____ Open wires, front sign. ____ Open wires, main room hanging from ceiling. ____ Open wires, south shop. On floor, west wall and south wall. ____ Cover plate for outlets needed x 3 in center office room. ____ Cover plate needed for exterior/rear electrical box. |
|
| 02/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. ____ Provide an appropriate working space in front of electrical equipment. |