Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/27/2008

Applicant:

HOLUALOA CENTRE EAST OFFICE LLC

Description:

FULL FIRE INSPECTION. THIS REPORT WAS GENERATED FOR THE MANAGEMENT COMPANY. THEY WERE NOT DOING THE WORK FOR THE OCCUPANTS. REFER TO T08FR00236.

Outstanding Inspections

Case Number: T08FR00566
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/27/2008 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ____ Label ELECTRICAL ROOM.
02/27/2008 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Violation 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. ____ Provide a working space around electrical service equipment.
02/27/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 905.9 Valve supervision. Valves controlling water supplies shall be supervised in the open position so that a change in the normal position of the valve will generate a supervisory signal at the supervising station required by Section 903.4. Where a fire alarm system is provided, a signal shall also be transmitted to the control unit. ____ Repair door to riser room. Door must be able to close and lock. ____ Secure main control valves in the normal open position. These are located on the east side of the property.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00566
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/11/2008 INSP - FULL JVINCENT Approved ALL VIOLATIONS CORRECTED 04/11/2008.