Case: T08FR00566

Parcel: 13414001K


Addresses:

7820 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR00566

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
02/27/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

____ Label ELECTRICAL ROOM.
02/27/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.

____ Provide a working space around electrical service equipment.