Case: T08FR00566

Parcel: 13414001K


Addresses:

7820 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR00566

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
02/27/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 905.9 Valve supervision. Valves controlling water supplies
shall be supervised in the open position so that a change in the
normal position of the valve will generate a supervisory signal
at the supervising station required by Section 903.4. Where a
fire alarm system is provided, a signal shall also be transmitted
to the control unit.

____ Repair door to riser room. Door must be able to close and lock.
____ Secure main control valves in the normal open position. These are located on the east side of the property.