Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/06/2007

Applicant:

LANGFAN WILLIAM K TR

Description:

Full Fire Protection Inspection (FPI) Conducted 6/4/07

Outstanding Inspections

Case Number: T07FR01084
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
06/13/2007 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____ Provide 18" clearance from sprinkler deflector, east cooler.
06/13/2007 VIOL - FIRE SERVICE FEATURES DGREENLE Correction Required Address not visible: TFC 505.1 - Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. _____ 1. Address shall be displayed in an approved manner. Manager received a copy of the "Pima County Address Display Requirements" flyer.
06/13/2007 VIOL - FIRE SERVICE FEATURES DGREENLE Correction Required TFC 508.5.4 - Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____ Remove vegitation obscuring FDC sprinkler inlets.
06/13/2007 VIOL - INT.FINISH, DEC. MATL'S DGREENLE Correction Required TFC 805.1 - General. In occupancies of Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall be flame resistant in accordance with Section 805.2 and NFPA 701 or be noncombustible. TFC 805.2 - Acceptance criteria and reports. Where required to be flame resistant, decorative materials shall be tested by an approved agency and pass Test 1, as described in NFPA 701, or such materials shall be noncombustible. Reports of test results shall be prepared in accordance with NFPA 701 and furnished to the fire code official upon request. _____ Banner above sushi bar.
06/13/2007 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____ The hood exhaust and extinguishing systems shall be inspected and tagged. _____ All deficiencies noted in the inspection report shall be corrected.
06/13/2007 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. _____ Automatic sprinkler system shall be inspected and tested. _____ All deficiencies found shall be corrected. _____ All extinguishers shall be serviced and tagged annually.
06/13/2007 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ Clean grease trap.
06/13/2007 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01084
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/11/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.