Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01084
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ Clean grease trap. |
|
06/13/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____ The hood exhaust and extinguishing systems shall be inspected and tagged. _____ All deficiencies noted in the inspection report shall be corrected. |
|
06/13/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. _____ Automatic sprinkler system shall be inspected and tested. _____ All deficiencies found shall be corrected. _____ All extinguishers shall be serviced and tagged annually. |