Case: T07FR01084

Parcel: 12212001A


Addresses:

4689 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR01084

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/13/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace batteries in emergency lighting.