Case: T07FR00818
Case Details
Entered Date:
04/26/2007
Applicant:
ROATH PROPERTIES LLC
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR00818
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 18
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | IFC 304.1.1 Accumulations of wastepaper, wood, hay, straw, weeds, litter or combustible or flammable waste or rubbish of any type shall not be permitted to remain in any vacant lot, yard, or open space. Remove storage of waste materials ( wood, other combustable waste stored in alley between the buildings on the West side of structure. Remove old appliances stored on patio near NW exit from structure.) |
04/26/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | IFC 308.3.1.1 LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Remove Gas barbeque grill from rear exit patio ( 10 feet back from building or combustible roofing). |
04/26/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | IFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. Remove combustables stored near hot water heater ( office near SW exit). |
04/26/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | IFC 315.2.2 Means of egress. Combustible materials shall not be stored in exits or exit enclosures. Remove Folding table that is blocking the front NE exit from the building. |
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Clear obstructions blocking electrical panel on W patio, in old Vip room ) |
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove all extension cords in use in the building. ( out door patio for lighting, N loung under booth, in bar, near stage, all other extension cords in use.) |
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 605.6 Approved covers shall be provided for all switch and electrical outlet boxes. Repair and/or replace covers for: 2 loose outlets on S lounge wall, East lounge, breaker box near NW exit, breaker box on W patio, office). |
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Cover open wire splices with approved junction boxes or covers (over main exit door, ceiling over booths on South end of bar, ceiling over E bar booths, over NE exit, W of stage near ceiling, office ceiling, storage closet near SW exit, in bar near breaker panel) |
04/26/2007 | VIOL - FIRE RESIST.RATED CONST | NSPRENGE | Violation | IFC 703.1 The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Repair openings in the dry wall and ceiling tiles in the E lounge, above the stage area. |
04/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Have kitchen sprinkler system inspected and maintained. Records of such inspections shall be maintained on the premises at all times. Have all portable fire extinguishers inspected annually and provide documentation of such. Have your commercial cooking hood extinguishing system inspected by a certified company and paperwork of such inspection provided for reinspection. |
04/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 906.5 Conspicuous location. Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. Mount extinguishers where they are easily seen. ( 3 in kitchen, 1 in bar) |
04/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 906.6 Fire extinguishers shall not be obstructed or obscured from view. Mount extinguisher in bar so as not to be obstructed by bar equipment. |
04/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Mount extinguishers on approved brackets. ( 3 in kitchen) |
04/27/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place. Post your occupant load in every room of assembly. |
04/27/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 1008.1.8.4 Manually operated flush bolts or surface bolts are not permitted. Remove surface bolts from all exit doors.(Rear exit doors ( West) and Front main exit door were noted.) |
04/27/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 1008.1.9 Each door in a means of egress from an occupancy of Group A or E having an occupant load of 100 or more and any occupancy of Group H-1, H-2, H-3 or H-5 shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Place panic hardware on all required exits with latches or locks. |
04/27/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 1011.1 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Place an illuminated exit sign over NW exit ( old Vip room) |
10/08/2007 | VIOL - COMPRESSED GASES | FCONTRER | Continued | I have been at this location from the begainning of the remodel,All codes almost complete,the hood system still needs to be removed, today maybe,Steve will call me when he gets done. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00818
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2007 | INSP - FULL | FCONTRER | Approved | This is a final inspection. The hood system was remove along with all cooking equipment.all violation written down by inspector Sprenger has been completed.Inspector MA18 was there to make sure this was completed. |