Case: T07FR00818

Parcel: 128010420


Addresses:

1120 S WILMOT RD


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00818

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
04/26/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Cover open wire splices with approved junction boxes or covers (over main exit door, ceiling over booths on South end of bar, ceiling over E bar booths, over NE exit, W of stage near ceiling, office ceiling, storage closet near SW exit, in bar near breaker panel)
04/26/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.6 Approved covers shall be provided for all switch and electrical outlet boxes. Repair and/or replace covers for: 2 loose outlets on S lounge wall, East lounge, breaker box near NW exit, breaker box on W patio, office).
04/26/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Remove all extension cords in use in the building. ( out door patio for lighting, N loung under booth, in bar, near stage, all other extension cords in use.)
04/26/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Clear obstructions blocking electrical panel on W patio, in old Vip room )