Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00818
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Cover open wire splices with approved junction boxes or covers (over main exit door, ceiling over booths on South end of bar, ceiling over E bar booths, over NE exit, W of stage near ceiling, office ceiling, storage closet near SW exit, in bar near breaker panel) | |
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.6 Approved covers shall be provided for all switch and electrical outlet boxes. Repair and/or replace covers for: 2 loose outlets on S lounge wall, East lounge, breaker box near NW exit, breaker box on W patio, office). | |
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove all extension cords in use in the building. ( out door patio for lighting, N loung under booth, in bar, near stage, all other extension cords in use.) |
|
04/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Clear obstructions blocking electrical panel on W patio, in old Vip room ) |