Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T07FR00660
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/09/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Remove equipment in office that is blocking access to your electrical panels.
04/09/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord connected to Rice cooker near SE Kitchen entrance.
04/09/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Replace missing electrical faceplates on SW corner of dining area and NW corner of dining room. Place blanks in two missing circuits in breaker box in office. Place cover/ juncion box over open socket in ceiling ( SE dining room near projection screen.) Replace missing balast in kitchen lighting and place open wiring splices in approved juction box.
04/09/2007 VIOL - FIRE RESIST.RATED CONST NSPRENGE Violation for and the maintenance of fire-resistance-rated construction and requirements for enclosing floor openings and 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Replace missing ceiling tiles ( 2 in office) , 1 in S hallway to bathrooms, 1 NW corner of dining area floor.
04/09/2007 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. You are hereby ordered to immediately STOP USE of all commercial cooking equipment until you have your extinguishing/hood systems immediately cleaned and maintain records of this cleaning.
04/09/2007 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used. 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. You are hereby ordered to have your hood and extinguishing systems serviced once every six monthes and maintain records of such.
04/09/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise’s electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate. You are hereby ordered to replace bulb or battery and cause you emergency lighting to operate over the South exit.
04/09/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1011.2 Illumination. Exit signs shall be internally or externally illuminated. Cause your exit signs to be lit. ( From kitchen Nside and Dining room N side)
04/09/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1011.5.3 Power source. Exit signs shall be illuminated at all times. Cause the back up power source to your exit sign on the South exit door to operate properly.
04/09/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1027.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. Your are hereby ordered to IMMEDIATELY remove any storage or accumulation of furniture or other objects obstructing your exit hall from the North dining room.
04/09/2007 VIOL - COMPRESSED GASES NSPRENGE Violation 3003.3.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. You are hereby ordered to secure the 3 large cylinders of CO2 in kitchen area near the South exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00660
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
04/10/2007 INSP - REINSPECTION NSPRENGE Approved Hood system cleaned overnight from roof to hood, commercial cooking equipment is now approved for use.
04/30/2007 COMPL - REINSPECTION NSPRENGE Approved