Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00660
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Replace missing electrical faceplates on SW corner of dining area and NW corner of dining room. Place blanks in two missing circuits in breaker box in office. Place cover/ juncion box over open socket in ceiling ( SE dining room near projection screen.) Replace missing balast in kitchen lighting and place open wiring splices in approved juction box. | |
04/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord connected to Rice cooker near SE Kitchen entrance. | |
04/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Remove equipment in office that is blocking access to your electrical panels. |