Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/06/2007

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full fire inspection done by Inspector John Bieg 4/6/07. "A-2" / Resturante.

Outstanding Inspections

Case Number: T07FR00649
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
04/06/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
04/06/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove compressed cylinders from blocking the electrical service equipment located by the exit door in the kitchen. A re-inspection is scheduled for 4/23/07.
04/06/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag the hood system located in the kitchen. { Submit plans for proper coverage of cooking equipment. }
04/06/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.5 There shall be a class K extinguisher located within a 30 foot travel distance of commercial-type cooking equipment.
04/06/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 There shall be a record of hood system cleaning on the premises.
04/06/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Mount the ABC portable fire extinguisher located in the kitchen.
04/06/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 #1. Remove the pad-lock from the walk in refer door and repair the inside door handle. #2. Remove the pad-lock from the beer cooler door and repair the inside door handle.
04/06/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 The exit door located in the kitchen shall have an approved exit sign.
04/06/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The exit sign located by the east exit shall be fully illuminated. #2. The exit sign located by the south exit shall be fully illuminated.
04/06/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Repair the emergency lighting located in the mens restroom.
04/06/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove the keyed deadbolt from the exit door located in the kitchen.
04/06/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 Secure the compressed gas cylinders located in the kitchen by the exit door.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00649
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/09/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 7/9/07. Inspector John Bieg.