Case: T07FR00649
Case Details
Entered Date:
04/06/2007
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full fire inspection done by Inspector John Bieg 4/6/07. "A-2" / Resturante.
Outstanding Inspections
Case Number: T07FR00649
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Comply with this code. |
04/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove compressed cylinders from blocking the electrical service equipment located by the exit door in the kitchen. A re-inspection is scheduled for 4/23/07. |
04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag the hood system located in the kitchen. { Submit plans for proper coverage of cooking equipment. } |
04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.5 There shall be a class K extinguisher located within a 30 foot travel distance of commercial-type cooking equipment. |
04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 There shall be a record of hood system cleaning on the premises. |
04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Mount the ABC portable fire extinguisher located in the kitchen. |
04/06/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 #1. Remove the pad-lock from the walk in refer door and repair the inside door handle. #2. Remove the pad-lock from the beer cooler door and repair the inside door handle. |
04/06/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.1 The exit door located in the kitchen shall have an approved exit sign. |
04/06/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 #1. The exit sign located by the east exit shall be fully illuminated. #2. The exit sign located by the south exit shall be fully illuminated. |
04/06/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 Repair the emergency lighting located in the mens restroom. |
04/06/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.6 Remove the keyed deadbolt from the exit door located in the kitchen. |
04/06/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Secure the compressed gas cylinders located in the kitchen by the exit door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00649
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 7/9/07. Inspector John Bieg. |