Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1011.2 #1. The exit sign located by the east exit shall be fully illuminated. #2. The exit sign located by the south exit shall be fully illuminated. |
|
| 04/06/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1011.1 The exit door located in the kitchen shall have an approved exit sign. | |
| 04/06/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1026.5 Repair the emergency lighting located in the mens restroom. | |
| 04/06/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.6 Remove the keyed deadbolt from the exit door located in the kitchen. | |
| 04/06/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 #1. Remove the pad-lock from the walk in refer door and repair the inside door handle. #2. Remove the pad-lock from the beer cooler door and repair the inside door handle. |