Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 901.6 Service and tag the hood system located in the kitchen. { Submit plans for proper coverage of cooking equipment. } |
|
| 04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 904.11.5 There shall be a class K extinguisher located within a 30 foot travel distance of commercial-type cooking equipment. | |
| 04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 904.11.6.3 There shall be a record of hood system cleaning on the premises. | |
| 04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 906.7 Mount the ABC portable fire extinguisher located in the kitchen. |