05/23/2007 VIOL - MOTOR FUEL DISPENSING CFUNKE Continued Inspected the red diesel tank. The tank pump is gas powered with a fuseable link. Shut off worked properly. Hose has breakaway and the tank is equiped with the proper venting. Electrical final for the other tanks in process.
06/07/2007 INSP - AST/UST CFUNKE Continued Paul Sudweeks 702-208-0475
06/07/2007 INSP - REINSPECTION CFUNKE Continued Vents on the Class III liquid tanks are approved.
06/07/2007 VIOL - ADMINISTRATION CFUNKE Continued The 1000 gallon tanks have been removed. The permit for the 5-250 gallon tanks will be issued with the fuel tanks.

Completed Inspections

Case Status: FIELD
Case Number: T07FR00276
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/07/2007 VIOL - FLAMMABLE LIQUIDS CFUNKE Approved Tanks were inerted to less than 5% O2 with dry ice. The two 1000 gallon union distributors tanks were removed.